D9412GV2/D7412GV2 | Troubleshooting Guide | 3.0 Troubleshooting
.
Bosch Security Systems, Inc. | 11/05 | F01U011024B 59
TTP20: Point Indicates a Short Circuit
When It Is Open
A
There might be points that share a common address.
Determine the configuration of the installed system as
described in Section
Procedure
4.1.1 Identifying the Point Expansion
Technologies Installed on the System
1. From the keypad, press [MENU/ESC], then press
[NEXT] until you see VIEW PT STATUS.
on page , Section 113
4.1.2 Setting Up the Control Panel on page 114, and
Section
2. If using a D1255 Keypad, press [ENT] three times.
If using a D1260 Keypad, press [VIEW PT
STATUS][Next][Status].
4.1.3 Identifying the Points Associated with Each
Point Expansion Technology . on page 115
If there is a point that appears as missing in View Point
3. Press [NEXT] repeatedly to view the status of each
point.
Status, this point might share an address with another
point.
Does the symptom occur for any programmed points, 9
and above?
If this symptom occurred after installing a new point,
remove the device from the system.
If the point shows anything other than missing in View
4.1.1
Refer to Section
Identifying the Point
Expansion Technologies Installed on the System
Point Status, change the new point’s address to
on
page
another unused address, and change the control panel
113.
programming to match.
If the point shows missing in View Point Status, there
Are any D9210B Access Control Interface Modules
connected to the control panel?
The on-board point is not working or is not
programmed correctly. Refer to TTP16 Point
Trouble on One of the Eight On-board Points
on page
57.
1. Using RPS software or your D5200 Programmer,
select RADXAXS → Door Profile.
2. Record the point number assigned to each
D9210B that is connected to the control panel
by viewing the Door Point prompt.
Is the affected point number assigned to a
D9210B?
The on-board point is not working or is not
programmed correctly. Refer to TTP16 Point
Trouble on One of the Eight On-board Points
on page
57.
Is the same point number assigned to more than
one D9210B?
The D9210B is not working or is not
programmed correctly. Refer to
TTP15 Point
Trouble and there are D9210B Card Access
Interface Modules Connected to the Control
Panel
on page 55.
You must assign all D9210B modules a unique point
number. Once you do this, you must also use RPS
software or the D5200 Programmer to view
RADXPNTS and complete the programming of the
point.
A
is noise on the data bus. Refer to TTP48 Noise on
Wire on page 102.
Table 54 Point Configuration MatrixExamine on page 117.
Do any rows in Table 54 identify a point used by more
than one point expansion technology?
The point expansion technology is either not working
or not programmed correctly. If the affected point is
connected to:
• a D8128C or D8128D OctoPOPIT Module, refer
to
TTP11 on page 26.
• a D8125 Zone Expansion Module, refer to TTP12
on page
30.
• a D8125MUX Multiplex Bus Interface, refer to
TTP13 on page 37.
• a D8125INV Wireless Interface Module, refer to
TTP14 on page 48.
• a D9210B Access Control Interface Module, refer
to TTP15 on page 55.
• one of the on-board points, refer to
TTP16 on
page
57.
There are points that share a common address. You must
assign each programmed point in the control panel a unique
addressable point. This requires changing one of the
duplicate addressable points to an unused programmed
point, and changing the programming in RADXPNTS to
match.