D9412GV2/D7412GV2 | Program Entry Guide | 5.0 RADXSKED EN | 115
Bosch Security Systems | 5/05 | F001U003636B
Default: Blank
Selection: 1 to 11, 13 to 24, 28, 29
S## Door 1 [through 8]
Default: No
Yes
Enable the sending
of No Entry Events
for Door #.
23
No Entry Events On: The
control panel can log No Entry
Events when an invalid token is
detected for a specific door. No
Entry Events include No Entry-
Secured, No Entry-Interlock, No
Entry-Unknown ID, and No
Entry-Level. These events can be
directed to print at a local
printer or send a report remotely
through phone routing. This
sked enables No Entry Events to
be reported for Door #.
Selection: Yes or No
This parameter enables the sending of
No Entry Events for Door #.
No
Do not enable the
sending of No
Entry Events for
Door #.
S## Door 1 [through 8]
Default: No
Yes
Enable the
reporting of No
Entry Events for
Door #.
24
No Entry Events Off: The
control panel can log No Entry
Events when an invalid token is
detected for a specific door. No
Entry Events include No Entry-
Secured, No Entry-Interlock, No
Entry-Unknown ID, and No
Entry-Level. These events can be
directed to print at a local
printer or send a report remotely
through phone routing. This
sked disables No Entry Events to
be reported for Door #.
Selection: Yes or No
This parameter disables the sending of
No Entry Events for Door #.
No
Do not enable the
reporting of No
Entry Events for
Door #.
28 Expanded Off-Normal Test Report: To generate this event, one or more points must be in an off-
normal state at the time the sked executes. In addition, any system trouble that is active also generates an
Expanded Off-Normal Test Report. Expanded Off-Normal Test Reports include the Off Normal Test
Report Event as well as the supplementary event at the time the report is generated.
The Event Log shows only a Test Report Event.
If none of these conditions exists at the time the sked executes, only a Sked Executed Event is generated
and the Off-Normal Test Report is not sent.
29 Non-Expanded Off-Normal Test Report: Non-Expanded Off-Normal Test Report Events are only sent
when any point is in the off-normal state from any area, but only sends the Off Normal Test Report
Event. Any system trouble that is active also generates a Non-Expanded Off-Normal Test Report.
The Event Log only shows a Test Report Event.
If none of these conditions exist at the time the sked executes, only a Sked Executed Event is generated
and the Non-Expanded Off-Normal Test Report is not sent.
To meet UL 864 daily Test Report requirements (when using two phone lines), you must still use Sked
Function Code 9, Test Report and program it to occur on a daily basis as per AHJ requirements.