D9412GV3/D7412GV3 | Operation and Installation Guide | 4.0 Installation
.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03 16
If a ground fault condition occurs, the keypads display
SERVC GND FAULT and the control panel transmits
a GROUND FAULT TROUBLE, AREA 1.
When the control panel recognizes that the ground
fault condition is corrected, and remains corrected for
between 5 to 45 consecutive sec, a Restoral Report is
sent.
The D9412GV3 and D7412GV3 Control
Panels log and print a Ground Fault event
as a Trouble Point 256 if communicating
in Modem IIIa
2
format. If communicating
in Contact ID format, the control panels
generate a Ground Fault (310) event.
4.5.3 Enabling Ground Fault Detection
To enable Ground Fault Detect Enable, lock (close)
the S4 Ground Fault Detect Pin on the control panel
(Figure 3).
Figure 3: Enabling Ground Fault Detection
EARTH GROUND
COMMON
BA TTER Y NEG AT IVE ONLY
BAT TER Y POSITIVE ONLY
REL AY A
REL AY B
REL AY C
+ AUX POWER
CLAS S 2 TRAN SFORM ER
16.5 VAC 40 VA 60 Hz
Model D 1640
Int e r nally Fused - Do not short
Requi res Unswitched Outlet
Do n ot share with ot her equi pment
S4 GROUND FAU LT DETECT
Ena bl ed
Di s a bled
RED
ON when communicating
OFF when idl e
Co mmercial Pr ot ect ed- Prem is es Control Pa n el
D9412G V3 Control Panel is UL Listed For Ce nt r a l Stat ion, Local , Aux iliar y , Propr i etar y, and Househol d
Fi re Alarm, and Cen t r a l Stat ion, Local , Police St ation Co nnec t, House hol d Burgl a r Al ar m and Encr ypt e d
Li ne Sec ur i ty when com m unicat ing via a net wor k .
System is intended to be checked by a Qualified Techni cian at least ever y 3 years.
Th e types of initiat ing ci rcui ts the cont rol panel has been approved f or are A, M, W, SS.
Th e types of si gnaling the control panel has been appr oved for are DAC, OT, NC
VOLTA GE RANGES
O pen 3. 7 - 5. 0 V DC Short 0.0 - 1. 3 VDC
N orm al 2. 0 - 3. 0 VDC
Reset Pin
Disab le al l except Bat t ery
Ch a r g ing an d P rogramming
PERI PHER AL DEVI CE CONNECTIONS
RED P OWER +
YEL L O W DAT A BU S A
GREEN DATA BU S B
BL A C K C OMMON
ZON EX OUT 1
ZONEX IN 1
N. F .P. A.
St y le 4.0
Si g na ling
Li ne
Ci rcu its
F01U143074- 02
LE Ds O ff Wh en Normal
YE L LO W - C hargi ng St atus
RED - Low Batter y - 12.1 VDC
10. 2 VDC - Batter y Loa d Shed
Thi s equi pment should be instal led in accordance with the NFPA 70 (Nati onal Elect r ical Code) and
NF P A 72 (Nati onal Fire Alar m Code ) for Loca l , Ce n t ral St a ti on, Pr opr iet ary and H ouse hold Fire War ning
Sys t e ms and under the limits of the Loca l Author ity Having Jur isdi cti on (National Fi re Prot ection
As s o ciation, Ba t t e rmarch Park, Qui ncy, M A 02269). Pr int ed inf ormation des cribing
pr o per instal lat ion,
oper at ion, testing, mai nt enance, evacu ation pl anning and repai r ser vice is t obe provi de d with this
equi pmen t.
D9412GV3
26
25
ZO NEX POWER +
24
ZO NEX COMMON
23
PHONE LINE SEIZED LED
TIP
RING
TELCO CORD MODEL D161
SDI Conn ect or
ZON EX OUT 2
ZONEX IN 2
Refer to the D94 1 2GV3/D 7412G V3 Ap proved App lication s Complian ce Guide (P/N: F01U 143069)
for Sy s tem Wiri ng Diagram, Iss ue A an d f or compatible sm oke det ect or s.
PO W ER SUPPLY REQUIREMENTS
The Power Su ppl y provide s a maxi mum of 1. 4 Amps for the Control Panel an d al l
A ccesso ry Device s. For Syst em L oadi ng, refer to the D 9412 G V3/ D74 12 GV3 O perat ion
an d Installat i on Gui de (P/N: F0 1U1430 70).
( P/ N: F01U1 43070) for Power Re qui rem en ts r elat ing to Terminals 6 an d 7 .
CA UTION:
Re f e r to the D 9412G V3/ D741 2GV3 Operation an d Installat i on Gui de
All external conn ection s exc e pt Ter m i nal 5 (battery positive) are i nher ent l y power
limited. Re quirem en ts f or ba ttery stan dby time might red uce allowable ou tput.
WARNI NG!
Mu lti-Batte ry in stallat i on re qu ires
Mo de l D 122/ D 122 L Du al Ba ttery
H ar n ess . Impro per installation can
be a fire hazard .
B at t er y: R epl ac e ever y 3 to
5 years with one or two Mod el
D126 or D1218 12 V Le ad Acid
B at t er i es.
Inco rr ect wiring will
dam age this equi pm ent .
PR OGRAMMABLE
ALARM OUTP UTS
Ter m inal s
SW I TCH ED AUX
and6
7
Ter minal 8
Oper at ion Moni tor LED
Pulses when Nor m al
Flickers whe n Ri n ging
GREEN
D5200/D5360
PRO G CONN
Po int 8, S3 Option
Cl o se d = 1 k
EO L
No r mal Operat ion
Open =AB- 12 UL
Be l l Box 220 k
25
Poi nt 3Point 4
161514
Point 1 Poi nt 2
1211 13
Poi nt 5Point 6
1817 19
Point 7 Poi nt 8
21
20
22
Suitabl e for dr y ind oor
use only.
Devi ces pow er ed by the
AUX powe r output must
be supervised.
Mini mum syst em req uirement s for Cl assification in accor dance with AN S I/SIA CP -01- 2000:
UL L ist ed and Cl assified cont rol uni t Model D9412GV3 , D7412G V3, or D7212G V3;
UL L ist ed and Cl assified keypad Model D1256, D1257, D1260, D1255, D 1255R, or D1255RW;
UL L ist ed Local Bell
WARNING !
To pr ev en t risk of
el ect ri c shock,
di sconn ect AC po wer
and t el ephon e lines
before servicing .
CA UT I ON: Avoi d dam age to Panel.
Do n ot connect 24 V to terminals.
Max imum ch ar ging cu rrent 1.4 A
Re set Pi n
Disab le Al l Exc ept Battery
Charging A nd Prog rammi ng
27
PR OG
CONN
26
25
24
Re s e t Pi n
Disab le Al l Ex c ept Battery
Ch a r g ing A nd Prog ram m i ng
27
PRO G
CO NN
26
25
24
2
1
1 - S4 Locked (Closed). Control panel detects
ground faults.
2 - S4 Unlocked (Open). Control panel does not
detect ground faults.
4.5.4 Ground Fault Specifications
Table 5 provides the impedance specifications for
detecting ground faults when any terminal or field
wiring is shorted to ground.
Table 5: Ground Fault Impedance
Specifications
Impedance Control Panel Detects Ground Fault
≤ 300 Ω
Yes
300 Ω to
200 kΩ
Detection depends upon the terminal
≥ 200 kΩ
No
4.5.5 Locking the Reset Pin
Locking the reset pin disables the control panel
(Figure 4). When the control panel is disabled, the
system ignores most keypad commands and points.
CALL FOR SERVICE appears in keypad displays
when the pin is locked down.
On-board relays (Terminals 6 and 7) and off-board
relays deactivate when the control panel is reset.
Terminal 8 has power when the relay is deactivated.
Activation interrupts power at that terminal. The on-
board relay (Terminal 8) remains deactivated when
the reset pin is locked in the disable position.
Releasing the reset pin from the closed position
resets the control panel. The control panel resets all
its timers, counters, indexes, and buffers. Any points
that restore after a reset do not generate Restoral
Reports.
If the reset pin is placed in the disable position when
all areas are armed, there must be an entry in the
Answer Armed program item. Refer to RPS
Parameters in the D9412GV3/D7412GV3 Program
Entry Guide (P/N: F01U170807).
Locking the pin in the disable position applies power
to the control panel and charges the battery while the
detection devices and keypads are installed.
Figure 4: Reset Pin
1 - Reset pin locked (closed)
2 - Reset pin normal (open)