D9412GV4/D7412GV4 v2.03 | Installation and System Reference Guide | 17.6 Programming Options
.
Bosch Security Systems, Inc. | 7/16 | F01U265457-09 100
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
you must limit certain programming features or options to specific values.
Table 36: UL 864 Programming Requirements
Product Feature/Option
Permitted in
UL 864? (Y/N)
Possible Settings
Settings Permitted in
UL 864
Phone 1 through 4 Yes 24 characters Program a valid phone number
Phone Supervision Yes 0 to 240 sec 10 to 200 sec
Alarm On Fail No Yes / No Set to No
Buzz On Fail Yes Yes / No Set to Yes
Two Phone Lines Yes Yes / No
Set to Yes when using PSTN
communications.
Expand Test Report Yes Yes/No Set to Yes
Fire Reports Yes Yes / No Set to Yes
R# Fire Supervisory
Missing
Required Yes/No Set to Yes
Test Reports Yes Yes / No Set to Yes
AC Fail Report Yes Yes / No Set to Yes
AC Restoral Report Yes Yes / No Set to Yes
Battery Missing Report Yes Yes / No Set to Yes
Low Battery Report Yes Yes / No Set to Yes
Battery Restoral Report Yes Yes / No Set to Yes
R# Service Start Report Required Yes / No Set to Yes
R# Service End Report Required Yes / No Set to Yes
R# Fire Walk St Report Required Yes / No Set to Yes
R# Fire Walk End Report Required Yes / No Set to Yes
R# Walk Test St Report Required Yes / No Set to Yes
R# Walk Test End Report Required Yes / No Set to Yes
AC Fail Time Yes 1:00 to 90:00 min Enter 1:00
AC Fail Display Yes 10 to 300 sec 10 to 200 sec
AC Tag Along Yes Yes / No Set to Yes
AC/Battery Buzz Yes Yes / No Set to Yes
Bat Fail/Restoral Report Yes Yes / No Set to Yes
Area 1 Area On
Required to
send system
status reports
Yes / No Set to Yes
A# Delay Restoral Yes Yes / No Set to Yes
Verify Time Yes 10 to 60 sec 60 sec