190 en | SDI2 Modules D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
4. Press [ENTER] at the Connection Test option. The keypad tests and shows the results
for:
– Link. Tests the network cable connection, and responds with OK or Failure.
– Gateway. Tests the connection to the gateway, and responds with OK or Failure.
– Internet. Tests the network cable connection, and responds with OK or Failure.
8.4 B820 SDI2 Inovonics Interface Module
The B820 SDI2 Inovonics Interface Module provides the control panel with a wireless
interface for RF points, Key Fobs and RF Wireless Repeaters. This device is only supported on
the SDI2 bus.
Table 8.4 B820 Module Capacities Per Control Panel
RPS supports the configuration of the enclosure tamper on each of the B820 Inovonics
Interface modules. Refer to Section Enclosure Tamper, page 179.
System Supervision Time
Select the RF device supervision interval. If no communication has been received from a
device within the configured amount of time, a device missing trouble will be generated.
Low Battery Resound
Select the amount of time to wait before resounding a persisted Low Battery trouble.
8.5 Wireless Repeater
The Wireless Repeater is a device that is independent of the SDI2 bus. It provides an ability to
extend the range of the B820 SDI2 Inovonics Interface Module.
D9412GV4 D7412GV4 D7212GV4
11 1
Default:4 hours
Selection: 0, 4 hours, 12 hours, 24 hours, 48 hours, 72 hours
None No wireless device supervision
4 hr Send a missing condition after 4 hr of no contact from the wireless
repeaters.
12 hr Send a missing condition after 12 hr of no contact from the wireless
repeaters.
24 hr Send a missing condition after 24 hr of no contact from the wireless
repeaters.
48 hr Send a missing condition after 48 hr of no contact from the wireless
receiver.
72 hr Send a missing condition after 72 hr of no contact from the wireless
receiver.
NOTICE!
For fire devices, the control panel sets System Supervision Time to 4 hours by default, and
RPS cannot change that setting. Modifying the selection in RPS for fire devices has no impact
on the programming.
Default: Never Resound
Selection: Never Resound, 4 hours, 24 hours
NOTICE!
For fire devices, the control panel sets Low Battery Resound to 24 hours by default, and RPS
cannot change that setting. Modifying the selection in RPS for fire devices has no impact on
the programming.