D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 33
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Keypad Programming of the R# Backup Device
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the ROUTE GRP 1 - 4 option.
2. At the ROUTE GRP 1 - 4 prompt, enter the route group number you wish to configure and
press [ENT]. The keypad reads RT GRP 1 PRIMARY, and then the current configuration
(for example, SDI 88 PATH 4).
3. Press [NEXT] to advance to the RT GRP 1 BACKUP option. The Primary device cannot be
set to No Device before setting the Backup Destination.
4. To change the configuration, press [ENT] when the current configuration shows, and
then press [NEXT] or [PREV] to scroll through the options, as listed in Section R# Backup
Device, page 32.
5. When the keypad reads the desired configuration option, press [ENT] to select it.
When the keypad reads Parameter Saved, your selection has been configured.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access Keypad Programming
and navigate to the Route Group 1 - 4 option.
2. At the Route Group 1 - 4 prompt, enter the route group number you wish to configure
and press [ENTER]. The keypad reads Rt Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4).
3. Press the Backup softkey. The keypad reads Rt Group 1 Primary, and then the current
configuration (for example, SDI 88 PATH 4). The Primary device cannot be set to No
Device before setting the Backup Destination.
4. To change the configuration, press the Edit softkey, and then press the Next or the
Previous softkey to scroll through the options, as listed in Section R# Backup Device,
page 32.
5. When the keypad reads the desired configuration option, press the Save softkey to select
it.
When the keypad reads Parameter Saved, your selection has been configured.
3.3.10 Route Group Categories
Fire Reports
Selecting Yes enables a report to be sent when the event occurs.
Table 3.6 Fire Reports
NOTICE!
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4
and D7412GV4), enable Fire Reports.
Report Selection Report Description
R# Fire Alarm Yes, No Fire Event
R# Fire Restore (Alarm) Yes, No Fire restoral from alarm
R# Fire Missing Yes, No Missing Fire point
R# Fire Trouble Yes, No Fire trouble
R# Fire Supervision Yes, No Fire supervisory
R# Fire Restore (T/M/S) Yes, No Fire restoral from trouble, missing, or bypass
R# Fire Cancel Yes, No Canceled fire alarm
R# Fire Sup Miss Yes, No Fire supervisory missing