8.4 Test Log for Aspirating Smoke Detectors in the FAS-420-TM
Series
Device number
Serial number of detector module
Serial number of housing base
--- Measurement value/set value
Commissioning
Visual check +/-
Negative pressure [Pa]
Sensitivity [%/m]
Alarm delay [s]
Air flow range [10-50%]
Fault delay [min]
Malfunction saving [yes/no]
Dynamic air flow [yes/no]
Localization [yes/no]
LOGIC·SENS
[yes/no]
Air-Pressure-Dependent Calibration [yes/no]
Air-pressure-independent calibration
[yes/no]
Height [m above sea
level]
Air pressure [hPa]
Fan voltage [9-13.5 V]
Airflow [m/sec]
Temperature [°C]
Obstruction malfunction
LED flashes +/-
Relay fails after delay +/-
Signal transmission to fire panel +/-
Cause eliminated, LED off +/-
Relay activates after drop below threshold +/-
Cause eliminated, LED saved +/-
Relay remains off for min. 100 secs +/-
Breakage malfunction
LED flashes +/-
Relay fails after delay +/-
Signal transmission to fire panel +/-
Cause eliminated, LED off +/-
Relay activates after drop below threshold +/-
Cause eliminated, LED saved +/-
Relay remains off for min. 100 secs +/-
Main alarm
LED flashes +/-
Relay activates after delay +/-
Signal transmission to fire panel +/-
LED saved +/-
Relay saved +/-
Localization
Blow-out time [10-255 secs]
Blow out fan [9-13.5 V]
Intake fan [9-13.5 V]
LED localization permanently at air sampling
opening A
[yes/no] /
[sec]