Modular Fire Panel Technical Data | en 149
Bosch Sicherheitssysteme GmbH System Information 09.2017 | 11.3 | F.01U.028.089
Signal inputs IN1/IN2
Max. length of CAN cable for
system networking
L
max
= 1000m, depending on configuration, cable type
and topology
Input voltage 20VDC to 30VDC
Maximum current consumption – Standby mode: 135mA at 24VDC
– In case of alarm: 225mA at 24VDC
Permissible operating temp. -5°C to 50°C
Permissible storage temperature -20°C to 70°C
Space required (H x W x D) 190 x 404 x 60mm
Weight Approx. 2kg
Installation of the device is described in MPCPanel Controller, page 84.
7.4.2 Remote Keypad
Display element TFT touch scree, 320x240 pixels, 127.5mm x 170mm
active area
Operating and display elements 22 buttons, 1 key switch, 12 LEDs, 1 reboot button
Interfaces CAN1, CAN2, ETH1, ETH2, USB, RS232
Signal inputs IN1/IN2
Permissible length of CAN cable
for system networking
L
max
= 1000m, depending on configuration, cable type
and topology
Recommended cable type for
CAN connection
J-Y-ST/Y2x2x0.8
Power supply connections DC1 (power supply),
DC2 (redundant power supply)
Input voltage 12VDC to 30VDC, from FPA‑5000 or FPP‑5000
Maximum power supply line
resistance
18Ω
Maximum current consumption – Standby mode: 140mA at 24VDC
– In case of alarm: 230mA at 24VDC
Permissible operating
temperature
-5°C to 50°C
Permissible storage temperature -20°C to 70°C
Housing material and color ABS plastic, light gray (similar to RAL7035)
Space required (H x W x D) 280 x 340 x 87mm
Weight approx. 3kg
Installation of the device is described in Remote Keypad, page 127.