38 en | Planning Modular Fire Panel
09.2017 | 11.3 | F.01U.028.089 System Information Bosch Sicherheitssysteme GmbH
Each BCM-0000-B module requires one UPS 2416 A Universal Power Supply.
Depending on the back-up time, a PMF 0004 A housing may be required instead of the PSF
0002 A housing for the power supply.
1
2
BCM
BCM
4
3
A6142SPU
A6
1
4
2SP
U
A6142SPU
A61
4
2SPU
EPH 0012 A
MPH 0010 A
A2000FS
PA
2
0
00FS
P
12 V / 45 Ah12 V / 45 Ah 12 V / 45 Ah12 V / 45 Ah
12 V / 45 Ah12 V / 45 Ah 12 V / 45 Ah12 V / 45 Ah
Figure3.8: Configuration of 1 to 4 BCM modules (frame installation)
Configuration with 5 to 8 BCM Modules in Wall Mounting Housings
2 BCM-0000-B modules on short panel rail
2 BCM-0000-B modules at the end of the long panel rail
The remaining BCM-0000-B modules on a panel rail in the center of the system.
Each BCM-0000-B module requires one UPS 2416 A Universal Power Supply.