Modular Fire Panel Installation | en 93
Bosch Sicherheitssysteme GmbH System Description F.01U.028.089 | 8.0 | 2011.07
Installation
The MPC Panel Controller can be installed in the following housings: CPH 0006 A,
MPH 0010 A, HCP 0006 A and HBC 0010 A.
For installation, follow the instructions on the following pages (Figure 4.44, Page 93 to
Figure 4.46, Page 95).
Notes:
Make sure the PRS 0002 A Panel Rail Short is installed before you install the panel
controller.
Secure the grounding cable at the screw provided on the housing (step 4 in Figure 4.45).
Plug the cable into the "IN" slot on the PRS 0002 A Panel Rail Short (step 6 in
Figure 4.45).
Caution: Connection at the "OUT" slot or to a PRD 0004 A Panel Rail Long is not
permissible.
Plug the terminal element for the data bus into the "OUT" slot on the last occupied PSD/
PRD panel rail (step 8 in Figure 4.46).
Figure 4.44 MPC installation (1-3)
3
PRS 0002 A
1
2