46 en | Product Description Modular Fire Panel
F.01U.028.089 | 5.4 | 2009.08 Product Information Bosch Sicherheitssysteme GmbH
1.15.11 NZM 0002 A Notification Appliance Zone Module
This module is used to connect two monitored primary lines for activating notification
appliances. Currents of up to 3 A per output are possible in conjunction with the HPD 0000
Power Distributor.
Technical specifications
1.15.12 RMH 0002 A Relay Module High Voltage
The module has two change-over contact relays (type C) for monitored connection of external
elements with feedback, e.g. electromagnetic door holders, fans, smoke dampers.Each relay
has one NO (normally open) contact and one NC (normally closed) contact, and is protected
by a 6.3 A fuse. The maximum permissible contact load is 5 A at 120 V/230 V AC and 5 A at
30 V DC. The relay module can also be used as an extinguishing system interface in
accordance with VdS 2496.
Labeling Connector
B OUT1 / A OUT1 / B IN1 / A IN1 NAC zone 1
B OUT2 / A OUT2 / B IN2 / A IN2 NAC zone 2
DC + / DC - External power supply via the HPD 0000 A Power
Distributor
BAT + / BAT - 24 V DC input, battery voltage
SYNC GND / SYNC OUT Output synchronization
SYNC GND / SYNC IN Input synchronization
Operating and display elements 4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (LED test)
Input voltage 20 V DC to 30 V DC / 5 V DC ± 5%
Maximum current consumption
- Standby mode (both zones)
- In the event of an alarm (both
zones)
40 mA
65 mA
Maximum output voltage 29.5 V DC
Maximum output current for:
- supply by panel rail
- external power supply
500 mA per NAC zone (in the event of an alarm)
3 A per NAC zone (in the event of an alarm)
Dimensions (H x W x D) Approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Weight Approx. 135 g (approx. 4.8 ounces)