Inspection and maintenance | 49
6720872361 (2017/04)Greenstar combi 100 p / 151 p
Heat exchanger
NOTICE:
Damage to the coating of the heat exchanger.
Cleaning of the heat exchanger should not be necessary until five
years after the initial commissioning.
Only use a Bosch cleaning blade and Bosch cleaning brush.
Only clean heat exchanger in case if soiling is clearly visible.
Heatronic boiler control
In case of a component defect, a fault is shown on the display.
The Heatronic boiler control monitors all safety and control components.
NOTICE:
The Heatronic boiler control can be damaged by leaking water.
Cover the Heatronic prior to working on water filled components.
Important notes
An overview of the faults can be found on page 56.
The following analytical tools are needed for service and
maintenance:
Electronic flue gas analyzer for CO
2
, O
2
, CO, and flue gas
temperature
(0 to 30 mbar)
pH Test strips
Glycol tester of antifreeze is being used
Special tools are not required.
Approved lubricants are:
For parts touched by water: Unisilkon L 641 (part-
# 8 709 918 413 0)
or fittings: HFt 1 v 5 (part-# 8 709 918 010 0).
Use part-# 8 719 918 658 0 as heat conducting paste.
Use only genuine Bosch spare parts.
Request spare parts.
Replace removed gaskets and O-rings with new ones.
HAfter the inspection/maintenance
Re-tighten all loosened threaded connections.
Restart the appliance ( page 36).
Check all connections used during maintenance for leaks.
Check the gas-air ratio.
14.1 Description of various steps
14.1.1 Calling up the latest fault (service function 6.A)
Select service function 6A (page 43).
An overview of the faults can be found on page 56.
14.1.2 Fresh water filter in the cold water pipe
Close cold water tap.
Depressurize the cold water pipe.
To access the filter remove the safety clip (step 1), pull out the pipe
(step 2), and remove the filter from the pipe (step 3).
If necessary, clean with plastic brush under running water.
Fig. 63 Strainer in the cold water pipe
14.1.3 Plate-type heat exchanger
If the DHW output on the combi boiler is significantly reduced:
Check filter in the cold water pipe for contamination ( Fig. 49).
Depressurize the appliance.
Remove plate type heat exchanger and replace
-or-
Descale with descaling agent approved for stainless steel (Grade
316-1.4401).
To remove the plate type heat exchanger:
Unplug electrical connections.
Remove hose from safety relief valve.
Fig. 64 Unplugging electrical connections / removing hose from safety
relief valve
6 720 641 933-92.1o
1
2
3
6 720 641 933-46.2O