Installation instructions
3.6 Gas piping & connections
Before connecting the gas supply, check the rating
plate on the right side of the heater to be sure that the
heater is rated for the same gas to which it will be
connected.
In the United States: The installation must conform with
local codes or, in the absence of local codes, the
National Fuel Gas Code ANSI Z223.1/NFPA 54.
In Canada: The Installation must conform to CGA B149
INSTALLATION CODES and/or local installation
codes.
GAS CONNECTIONS
B Install a manual gas shut off valve on the gas supply
line.
B Install a union when connecting gas supply.
B The minimum internal diameter required for
any appliance connector is ¾”, see Fig. 13 for
more details on pipe sizing.
B National Fuel Gas Code requires that a sediment
trap (drip leg) be installed on gas appliances not so
equipped. The drip leg must be accessible and not
subject to freezing conditions. Install in accordance
with the recommendations of the serving gas
supplier, see Fig. 2.
Fig. 11 Gas connection
Once connections are made, check for gas leaks at all
joints. Apply some gas leak detection solution to all gas
fittings. Bubbles are a sign of a leak. A combustible gas
detector may also be used to detect for leaks.
GAS LINE SIZING
The gas supply piping for a single heater should be
sized for a maximum draw of 199,000 BTUH. Measure
the length of gas supply line from the building's gas
main to the heater and use the tables in Fig. 13, page
11 or the gas line manufacturer’s sizing tables to
determine the pipe diameter necessary. If there are
more gas drawing appliances on the line, size the gas
line according to the total maximum amount of BTU
draw input rating of for all appliances combined.
Note: Undersizing the gas line may result in diminished
hot water flow rate and temperature. See chapter 3.13,
page 26 for the procedure to measure gas pressure.
Proper gas pressure must be confirmed at time of
installation.
Fig. 12
Warning: DO NOT connect to an
unregulated or high pressure propane
line or to a high pressure commercial
natural gas line.
Warning: The heater must be isolated
from the gas supply piping system
during any pressure testing of that
system at test pressures equal to or
more than 0.5 psig. If overpressure has
occurred, such as through improper
testing of the gas lines or malfunction of
the supply system, the gas valve must
be checked for safe operation.
Gas supply
Cap
Minimum
3”
Danger: If you have a leak, shut off the
gas. Tighten appropriate fittings to stop
leak. Turn the gas on and check again
with a gas leak detection solution.
Never test for gas leaks using a match
or flame.
Gas piping
Inlet gas particle screen
(included)