Callout Description
1 Used for Minor Attack programming
2 Used for Major Attack programming
3 Used for enabling, or disabling the reed switch
Minor Attack setting
The location of the jumper determines how many repetitive taps (single vibrations) detected
by the sensor in a minor attack. The Minor Attack setting is either enabled or disabled,
depending on the positioning of the jumper. If enabled, there are two sensitivity settings:
Low. Requires 8 taps to generate an alarm
High. Requires 4 taps to generate an alarm
When a tap occurs, a 90-sec timer starts. If the tap exceeds the four or eight count threshold
within 90-sec, an alarm is transmitted.
Notice!
A single tap such as a branch in the wind lightly brushing a window can start the minor attack
timer and tap count. To avoid false alarms, do not use the Minor Attack setting where stray
vibrations might occur.
100 en | Device Specifications and Overview Easy Series Control Panel
2014.09 | 01 | F.01U.306.221 System Reference Guide Bosch Security Systems, Inc.