RPS Configuration Items
Programming Item Item
Number
Selections Manuf.
Defaul
t
RPS Passcode 118 6 digits, using 0 to 9 and A to F. 12345
6
RPS Automatic Call In Frequency 224 0 = Never
1 = Daily
2 = Weekly
3 = Monthly
RPS Automatic Call In Time (Hours) 225 0 to 23
RPS Automatic Call in Time
(Minutes)
226 0 to 59
RPS Automatic Call in Time (Day of
Week)
227 0 to 6, where 0 = Sunday and 6 = Saturday
RPS Automatic Call in Time (Day of
Month)
228 1 to 28
RPS Automatic Call in Phone
Number
229 Enter a phone number (up to 32 digits) or IP address
(000.000.000.000 to 255.255.255.255) for each
destination:
0 to 9 = [0] to [9]
* = [*][*]
# = [*][#]
Pause = [*][1]
Exit with save = [#]
Exit without save = [#][#]
Press [#] twice within two seconds to exit without
saving your entry.
Disable phone number = [0][#]
Disable IP address = 240.0.0.0
RPS Automatic Call in Method 245 0 = Phone number
1 = IP address
RPS Port Number 246 0 to 65535 7750
Route Reporting Options
Point Report and Restoral Routing
Programming Item Item
Numbe
r
Manuf.
Default
Programming Item Item
Numbe
r
Manuf.
Default
Point Reports and Restorals (all)* 301 3 Fire Trouble 328 3
Intrusion Alarm 307 3 Fire Trouble Restoral 329 3
Intrusion Alarm Verified 308 3 24-Hour Trouble 331 3
5.2.4