Wireless Sensitivity (9018 ... 9328): Points 1 - 32 = 0
Alarm Verification (9016 ... 9326): Points 1 - 32 = 0
Table 5.2: Manuf. Default for Point Programming Items
Output Programming Items
Programming Item Item
Number
Selections Manuf.
Defaul
t
Fire Output Cadence 600 0 = Temporal Code 3 cadence
1 = Pulse cadence
(two-sec on, two-sec off)
0
Output 1 Function (wired) 611 0 = Disabled
1 = Intrusion
2 = Intrusion Latching
3 = Fire
4 = Fire Latching
5 = Intrusion and Fire
6 = Intrusion and Fire Latching
7 = System Reset
8 = System On
9 = System Ready
10 = Key Fob On/Off
11 = Key Fob 2-sec Pulse
13 = User Controlled
14 = Interior Intrusion and Fire
15 = System On (Unoccupied)
16 = Intrusion and Fire 2
5
Output 2 Function (wired) 621 5
Output 3 Function (wired) 631 5
Output 4 Function (wired) 641 7
Output 4 Supervised Speaker Driver
(wired)
642 0 = Supervised 8 Ω speaker driver
1 = Unsupervised open collector
0
Default = Country-specific default. Select this programming item to hear the updated default value, or refer to
Country Code Specific Default Programming Codes, page 112.
See also
Country Code Specific Default Programming Codes, page 112