18 MU 100 – 6721804146 (2019/10)
2.4 Specification
This product conforms to European directives and
supplementary national requirements in design and
operation. Compliance is demonstrated by the CE
marking.
You can request the conformity declaration of the product. If
you require this, contact the address on the back cover of these
instructions.
Table 3
Table 4 Measurements of low loss header temperature
sensor (T0), combined e.g. CW 400
Table 5 Measurements of low loss header temperature
sensor (T0), combined RC310
2.5 Additional accessories
For detailed information about suitable accessories, refer to
the catalogue or Internet page of the manufacturer.
Low loss header temperature sensor; connection to T0
Primary pump; connection to PC0
Installation of additional accessories
Install the additional accessories in accordance with legal
regulations and the instructions supplied.
2.6 Cleaning
Wipe the casing with a damp cloth when necessary. Never
use aggressive or caustic cleaning agents for this.
Specification
Dimensions (W × H × D) 151 × 184 × 61 mm
(for more dimensions
Fig. 7 at end of document)
Maximum conductor cross-
section
230 V terminal 2.5 mm
2
Extra-low voltage terminal 1.5 mm
2
Rated voltages
• BUS •15VDC
(reverse polarity
protected)
Module mains voltage 230 V AC, 50 Hz
•User interface •15VDC
(reverse polarity
protected)
Pump, solenoid valve,
interference output
230 V AC, 50 Hz
Fuse 230 V, 5 AT
BUS interface EMS and EMS 2/EMS plus
Power consumption
Standby
< 3 W
Max. power output
per connection(PC0)
per connection(OE1)
400 W (high-efficiency
pumps permissible:
<30A for 10ms)
120 W (high-efficiency
pumps permissible:
<30A for 10ms)
Permitted ambient
temperature
0 ... 60 °C
IP rating IP 44
Protection class I
ID no. Data plate ( Fig. 21 at the
end of document)
Temperature of ball thrust
test
75 °C
Degree of pollution 2
°C °C °C
20 14772 50 4608 80 1704
25 12000 55 3856 85 1464
30 9786 60 3243 90 1262
35 8047 65 2744 95 1093
40 6653 70 2332 100 950
45 5523 75 1990 – –
°C °C °C
20 12486 50 3605 80 1256
25 10000 55 2989 85 1070
30 8060 60 2490 90 915
35 6536 65 2084 100 677
40 5331 70 1753 – –
45 4372 75 1480 – –