64 en | Connection Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
5.8 Fireman’s Panel
5.8.1 Voice alarm controller
Connect the fireman’s panel to the voice alarm controller (see section 5.1.5 ).?
5.8.2 Remote control extensions
The fireman’s panel has 1 socket for remote control extensions (Remote Control Extension,
Remote Control Extension kit). Use shielded Cat-5 Ethernet cables with RJ45 plugs to
connect a remote control extension to the fireman’s panel. When the system requires more
than 1 remote control extension, use the system sockets on the remote control extension to
make loop-throughs. See section 5.4.2 for connection details.?
5.8.3 Status output contacts
The fireman’s panel has 3 status output contacts to indicate the current system state. The
procedure for connecting the status outputs is the same as the procedure for connecting
status outputs to the voice alarm controller (see section 5.1.11 ).
5.8.4 Power
The procedure for connecting a fireman’s panel to a power supply is the same as the
procedure for connecting a remote control to a power supply (see section 5.4.4 ).