72 en | Configuration Plena Voice Alarm System
9922 141 1037x (V2.16) | V0.6 | 2011.09 Installation and Operation manual Bosch Security Systems B.V.
Table 6.7 Call station DIP switches
6.4.1 Call station ID
The ID of the call station is set using switches 1 to 4. Each call station must have a unique ID
(1 to 9).
6.4.2 Sensitivity
The sensitivity of the call station is set using switches 5 and 6 (see Table 6.8).
Table 6.8 Call station sensitivity
6.4.3 Speech filter
If switch 7 is in the ON position, a speech filter is activated for the call station. The speech
filter improves the speech intelligibility by cutting off the lower frequencies.
6.4.4 Termination
The last call station in a sequence of looped-through call stations must always be terminated.
Only for these call stations, put switch 8 in the ON position.
6.5 Remote control
The remote controls are configured using a DIP switch (see Figure 6.8).
Figure 6.8 Remote control settings
6.5.1 Remote control ID
The ID of the remote control is set using the RCP ID switch. The ID of the remote control must
be the same as the number of the Remote Control Panel connection of the voice alarm
controller to which the remote control is connected (1 to 2). Actions that are started by the
remote control with ID 1 have a higher priority than actions that are started by the remote
control with ID 2.
DIP switch Description
1, 2, 3, 4 Set the ID of the call station. See section 6.4.1 .
5, 6 Set the sensitivity of the call station. See section 6.4.2 .
7 Switches the speech filter on (ON) and off (OFF). See section 6.4.3 .
8 Switches termination on (ON) and off (OFF). See section 6.4.4 .
Sensitivity Switch 5 Switch 6
-15 dB OFF OFF
0 dB OFF ON
6 dB ON OFF
Reserved ON ON