7.4 Emergency state
Emergency calls can only be distributed when the system is in the emergency state. See
section 7.4.1 for information about entering the emergency state. In the emergency state, it is
possible to distribute the following emergency calls:
Live speech with the emergency microphone of the voice alarm controller or remote
controls (see section 7.4.4 ).
The default alert message (see section 7.4.7 ).
The default alarm message (see section 7.4.8 ).
7.4.1 Enter the emergency state
To enter the emergency state, push the emergency button on the front of the voice alarm
controller or the remote controls (see Figure 7.8). The red LED that is integrated in the switch
lights. The emergency state can also be entered by pushing the Emergency button on the
fireman’s panel.
Figure 7.8 Emergency button
At the moment the emergency state is entered, a beeper starts and the EMG status output
contact are closed. See section 7.4.3 for information about exiting the emergency state.
NOTICE!
It is not possible to distribute chimes or speech with the call station when the system is in the
emergency state, because the call station is disabled automatically at the moment that the
system enters the emergency state.
NOTICE!
It is also possible to distribute emergency calls using emergency trigger inputs. When an
emergency trigger input is activated, the system automatically enters the emergency state and
takes the action that is programmed with the configuration software.
NOTICE!
See the Configuration Software Manual (9922 141 1038x) for more information about the
configuration software.
Indicator test
EMG mic
Alert message
Alarm message
All call