Bosch Security Systems | 2005-10 | 9922 141 10384 en
Plena Voice Alarm System | Software Manual | Messages en | 30
6.5.3 Create a mergeable message
Proceed as follows:
1 Click the New button. A New message window
appears.
2 Enter a name for the new message in the New
message window and click the OK button. The
name of the new message appears in the Edit
messages window.
3 Select the mergeable message template from the
Template drop-down list.
4 Attach wave files to the Variant components of the
template. These have green Wave file fields.
5 Click the Save button to save the changes.
6.5.4 Example
In this example, a mergeable message is created that is
used to evacuate floor 1 of the visitors’ wing in a hotel.
The message is based on the template that was created
in section 6.4.3. The template components are:
An alert chime to attract the attention. The name of
the wave file that contains the alert chime is alert
chime in this example.
Speech: ‘Due to an emergency, it is necessary to
evacuate’. The name of the wave file that contains
the speech is evacuate in this example.
Speech: ‘Floor’. The name of the wave file that
contains the speech is floor in this example.
Speech that contains the number of the floor. As this
is different for each floor, this component is a
Variant. To this component a wave file is assigned
that the word ‘one’. The name of the wave file that
contains the speech is one in this example.
Speech: ‘Immediately’. The name of the wave file
that contains the speech is immediately in this
example.
When the voice alarm controller plays this message, the
spoken part of the message is ‘Due to an emergency, it is
necessary to evacuate floor one immediately’.
Proceed as follows:
1 Open the Edit messages window.
2Click the New button. A window similar to the one
in section figure 6.16 appears.
3 Enter the name of the new message (for example,
Floor 1 evacuation) and click the OK button. The
name of the new message appears in the Edit
messages window (see figure 6.17).
Note
The procedure below is the general procedure.
See section 6.5.4 for an example.
figure 6.16: Example, step 2
figure 6.17: Example, step 3