Bosch Security Systems | 2005-10 | 9922 141 10384 en
Plena Voice Alarm System | Software Manual | Messages en | 31
4Select Floor evacuation from the Template drop-
down list to create a message that is based on the
Floor evacuation template. All components of the
template are copied to the message (see figure 6.18).
5Select one from the Wave file drop-down list in row
4 (see figure 6.11).
6 Click the Save button to save the changes.
The Floor evacuation template can also be used to create
a evacuation message for floor 2. Instead of assigning a
wave file that contains the word ‘one’ to the Variant, a
wave file containing the word ‘two’ must be assigned to
the Variant (see figure 6.20 for an example). When voice
alarm controller plays this message, the spoken part of
the message is ‘Due to an emergency, it is necessary to
evacuate floor two immediately’.
When the voice alarm controller receives a command to
play the messages Floor 1 evacuation and Floor 2
evacuation simultaneously and both commands have
the same priority, the messages are merged. The spoken
part of the merged message is: ‘Due to an emergency it
is necessary to evacuate floor 1, 2 immediately’.
6.5.5 Listen to messages
Proceed as follows:
1Click the > button in the Play field of a message to
listen to the message.
figure 6.18: Example, step 4
figure 6.19: Example, step 5
figure 6.20: Example, Floor 2 evacuation