Fig.7-17: Digital outputs
Observe the color-coding of the connectors.
Number of outputs 8
Connection method 2-wire connection
Output type ● Semiconductor out‐
puts, non-saving
● Protected,
with auto‐
matic restart
● Current-carrying
Electrical isolation to U
S
No
Electrical isolation to U
L
Yes
Output voltage, nominal value 24 V
Rated output current:
Nominal value
Maximum value acc. to DIN EN 61131-2
Signal 1
Signal 0 (leakage current)
UL rating:
General Purpose
Tungsten
0.5 A
≤ 0.6 A
2 mA ... 0.6 A
≤ 0.5 mA
0.5 A
5 W
Maximum total current of outputs 2 A