Parallel connection of outputs Yes, but only within one ter‐
minal
Output delay time < 500 μs
Contactor size (at 1 Hz) SG1 (6.2 W)
Lamp load (at 8 Hz) 5 W
Switching frequency
With ohmic load
With inductive load
100 Hz
Function (contactor)
Overload protection:
● Typical current level, causing switch-off
● Minimum current level, causing switch-off
●
Automatic restart with reduced load
1.2 A
0.6 A
After approx. 10 ms
Display overload Red collective LED for all 8
outputs
Voltage reduced on circuit interruption in the nominal
operating mode
Electronically limited to (Vext
– 50 V) type 26 V
Reverse voltage protection Ensured without connected
load
Supply voltage according to EN 61131-2 24 VDC
No-load current consumption from U
S
Typ. 50 mA
Cable length (unshielded) < 100 m
Fig.7-18: Data of digital outputs
Light-emitting diodes indicating the current status of the outputs are arranged
above the output terminals.
LEDs 1, 2, 3, 4
Meaning
Off The assigned output is not set.
Yellow The assigned output is set.
Fig.7-19: Status LEDs of digital outputs
An additional two-color light-emitting diode (identified by D) emits green light in
case the 24 V voltage is present and red light in case of a short-circuit or over‐
load.
Light-emitting diode
D
Meaning
Off 24 V voltage is missing.
Green 24 V voltage is present.
Red Short-circuit or overload.
Fig.7-20: Light-emitting diode D
32/54 Bosch Rexroth AG | Electric Drives
and Controls
Rexroth IndraControl L10 | Project Planning Manual
Connections and Interfaces