U
M
U
S
U
L
U
Rexroth Inline
U
LS
U
LS
IndraControl
PWR IN
24 PWR IN
24 SEG/F
ANA
GNDL
PWR IN Voltage terminal at IndraControl L45/L65/L85
R-IL 24 PWR
IN
Power terminal
R-IL 24 SEG/
F
Segment terminal with fuse
Fig.7-10: Inline supply and analog circuit
For comments on the wiring, please refer to chapter 8.3 "Electric Installation"
on page 54.
7.3 Digital Inputs and Outputs
7.3.1 Address Assignment of Inputs and Outputs
The eight digital inputs and outputs that are available on the slots 1 to 4 of the
IndraControl L45/L65/L85 (from left to right) are assigned to LEDs and bit ad‐
dresses according to the following table:
Eight digital inputs Eight digital outputs
Slot 1 2 3 4
Status LED 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Byte-bit
view
Bytes IX0.0 – 0.7 (default) QX0.0 – 0.7 (default)
Bit 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
Terminal
connector
set S01
Terminal point (signal) 1.1 2.1 1.4 2.4 1.1 2.1 1.4 2.4 1.1 2.1 1.4 2.4 1.1 2.1 1.4 2.4
Terminal point (24 V) 1.2 2.2 1.3 2.3 1.2 2.2 1.3 2.3 - - - - - - - -
Terminal point (last ground) - - - - - - - - 1.2 2.2 1.3 2.3 1.2 2.2 1.3 2.3
Terminal
connector
set S04
Terminal point (signal) 1.1 2.1 1.4 2.4 3.1 4.1 3.4 4.4 5.1 6.1 5.4 6.4 7.1 8.1 7.4 8.4
Terminal point (24 V) 1.2 2.2 1.3 2.3 3.2 4.2 3.3 4.3 - - - - - - - -
Terminal point (last ground) - - - - - - - - 5.2 6.2 5.3 6.3 7.2 8.2 7.3 8.3
Fig.7-11: Address assignment of inputs and outputs
7.3.2 Digital Onboard Inputs
The section on the left side of the connector panel provides eight digital inputs
as onboard inputs.
Bosch Rexroth AG DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
38/81
Connections and Interfaces