Slots 1 and 2:
Fig.7-12: Digital inputs at connector set S01
Observe the color-coding of the connectors!
Number of inputs 8
Connection method 2-wire connection
Electrical isolation to U
S
No
Electrical isolation to U
L
Yes
Reverse voltage protection Yes
Input voltage:
- Nominal value for "0
"
- Nominal value for "1"
-3 V ... +5 V
11 V ... 30 V
Input current:
- Nominal value for "0"
- Nominal value for "1"
< 2.5 mA
2.8 mA ... 6 mA
Delay time:
- for "0" after "1"
- for "1" after "0"
Typ. 50 μs
Typ. 50 μs
Current consumption by 24 V supply Typ. 60 mA
Cable length (unshielded) < 100 m
Interrupt inputs 8