Rated output current:
- Nominal value
-
Maximum value acc. to DIN EN 61131-2
- Signal 1
- Signal 0 (leakage current)
UL rating
- General purpose
- Tungsten
0.5 A
<= 0.6 A
2 mA ... 0.6 A
<= 0.5 mA
0.5 A
5 W
Maximum total current of outputs 2 A
Parallel connection of outputs Yes, but only within one terminal
Output delay time < 500 µs
Contactor size (at 1 Hz) SG1 (6.2 W)
Lamp load (at 8 Hz) 5 W
Switching frequency
●
With ohmic load
● With inductive load
100 Hz
Function (contactor)
Overload protection:
● Typical
current level, causing
switch-off
● Minimum current level, causing
switch-off
● Automatic restart with reduced load
1.2 A
0.6 A
After approx. 10 ms
Display overload Red collective LED for all
8 outputs
Voltage reduced on circuit interruption
in the nominal operating mode
Electronically limited to (V
ext
– 50 V)
Typ. 26 V
Reverse voltage protection Ensured without connected load
Supply voltage according to EN 61131-2 DC 24 V
Open-circuit power consumption from US Typ. 50 mA
Cable length (unshielded) < 100 m
Fig.7-17: Data of digital outputs
The output terminals are provided with LEDs that display the respective state
of the outputs.
LED 1, 2, 3, 4 Meaning
Off The assigned output is not set.
Yellow The assigned output is set
Fig.7-18: Status LEDs of digital outputs
An additional two-color LED (identified by D) emits green light in case the 24 V
voltage is present and red light in case of a short-circuit or overload.
Bosch Rexroth AG DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
42/81
Connections and Interfaces