● On
delivery, the shield connector is intended for the connection of thicker
lines ②.
● Remove the clip ③, turn the clip according to the cross-section of the line
used ④, and fit in the clip ⑤.
● Figure ⑥ shows the clip if a thin line is used.
8.3.8 Use of IndraControl L45/L65/L85 above 2700 m above MSL
The IndraControl L45/L65/L85 is designed for use up to 2700 m above MSL
according to DIN 60204.
If it is used above 2700 m above MSL, Bosch Rexroth cannot as‐
sume
warranty. Therefore the user assumes responsibility if it used
above 2700 m above MSL.
To use it above 2700 m, the user has to take appropriate measures. This con‐
cerns
mainly the track resistance. For use up to 4000 m above MSL Bosch
Rexroth recommends the following measures:
● Use of an isolating transformer between the AC 440 V and AC 230 V net‐
work.
● Generation of DC 24 V supply voltage with the "VAP01.1H-W23 024-010-
NN" Bosch Rexroth power supply unit, order code R911171065 (parts
number).
Circuit proposal
PE
PE
PE
PE
PE
PE
PE(1)
6 mm²
(green/yellow)
16 mm
²
(green/yellow)
min. 16 mm
² (
green/yellow)
PE neutral point
230V
400V
4 mm
²
(green/yellow)
16 mm
²
(green/yellow)
4 mm
²
(green/yellow)
Fuses, better: motor protective switches
Overvoltage
Transformer
Terminals in
e.g. drives
W1
N
V1
U1
L1
L2
L3
N
leads
L1.1
L2.1
L3.1
N
PE
PE
N
U2
PE
N1
U2
4 mm
²
(green/yellow)
230 V supply
Length max. 4 m
Power supply unit
VAP01.1H-W23
024-010-NN
+24 V
0 V
DC 24 V
all housing parts (functional earth)
to the device
to the housing of the control cabinet
category III
Overvoltage
category II
Overvoltage
category I
according to
EN 60742
isolated arrangement
operator terminals
service plug receptacle(s)
N conductor:
Operation only with
permission of the
operator!
- PE bars should be preferably installed on the mounting plate.
(1)
- In the case of isolated PE bars both ends must be connected
to the mounting plate by means of copper strips with a maximum
length of 20 cm.
- The cross-section of the copper strips has to be at least equal
to that of the incoming cable.
Fig.8-15: Circuit proposal