Nominal value DC 24 V
Tolerances -15 % / +20 % (without residual ripple)
Residual ripple ±5 %
U
max
30 V
U
min
19.2 V
Fig.4-1: Operating voltage according to DIN EN 61131-2
Three operating voltages are to be applied on the IndraControl L45/L65/L85
(see chapter 7.2.1 "Supply Voltages to be Connected Externally" on page
32). Taking the function modules and Inline terminals into consideration, the
current consumption from these voltages is:
Ensure that a ground terminal is always connected. In this way
malfunctions
that are caused by feed backwards via I/O signals can
be avoided.
Current consumption for
U
LS
at nominal voltage and
maximum extension
IndraControl L 45
IndraControl L 65
IndraControl L 85
2.6 A max.
3.0 A max.
3.0 A max.
Current consumption for U
M
and U
S
Max. of 8 A in total
Fig.4-2: Current consumption
4.3 Ambient Conditions
In operation Storage / Transport
Maximum sur‐
rounding air
temperature
+5 ... +55 °C -25 ℃ to +70 ℃
Relative humid‐
ity
RH-2; 5 % to 95 % acc. to
DIN EN 61131-2,
non-condensing.
RH-2; 5 % to 95 % acc. to
DIN EN 61131-2,
non-condensing.
Bosch Rexroth AG DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
20/81