Data loss caused by incorrect switch-off with-
out UPS
NOTICE
In case of a missing UPS, switch off the control cabinet PC via the software of
the operating system only and not by interrupting the current supply. This ap-
plies particularly for RAID systems.
12.2 Operating and error displays
There are four LEDs on the connector panel of the IndraControl VPB 40.3 to dis-
play the device states and errors. Apply the specified measure if one of the fol-
lowing LEDs indicates either an error or a note, see tab. 12-1 "LEDs for ope-
rating and error display on the connector panel" on page 42.
Some LEDs, e.g. the CPU temperature monitoring, are only active if
the service software has been configured accordingly.
LED Display Meaning Action
V
in
LED green Normal operation
LED off No supply voltage (24 V DC) Check the supply voltage at
the power supply unit!
TEMP LED off Normal operation
LED is flashing
red (flashing
frequency ap-
prox. 2 Hz)
Fan is not rotating or is rotating too slowly Check fan on the control cabi-
net PC!
LED red Overtemperature Reduce the ambient tempera-
ture!
UPS LED off Normal operation
LED red The control cabinet PC is currently operating
in battery mode, i. e. no supply voltage is
available!
Restore the power supply and
initiate a controlled restart!