Available slots per PC box type
PC box type Slot A1 Slot A2 Slot A3 Slot A4
Type L PCI PCI – –
Type M PCI PCI PCI PCI
Type N PCI PCIe – –
Type P PCIe PCIe – –
Type Q PCI PCI PCIe PCIe
Type R PCIe PCIe PCIe PCIe
Power drain of the extension cards
The total power allowed to be drained from the slots depends on the processor
used (refer to the following table).
Ambient temperature Intel® Celeron®
C3955U 2.0 GHz
Intel® Core™ i5-6300U
2.4 GHz
Intel® Core™ i7-6820EQ
2.8 GHz
Up to 35 °C 111 W 111 W 81 W
35 °C to 45 °C 70 W 70 W 50 W
10 Mounting, demounting and electric installation
10.1 Installation notes
10.1.1 Cables routing
● Lay all connecting cables in loops and use strain reliefs for all cables
● Keep the maximum distance possible from interference sources
● Do not route the CDI and CDI+ cables in parallel to motor cables or to other
noise sources, as the CDI connection can be disturbed
10.1.2 Housing distances for maintenance tasks
Provide a space on all sides of the device for sufficient cooling and cable routing
Comply with the following housing distances to execute maintenance tasks
directly at the device in the control cabinet:
● To maintain the fan and exchange the battery, go up by 120 mm (refer to the
following figure)
● For changing the hard disk 150 mm to the front (refer to the following figure)
● In the installed state, the internal connections of USB, mSATA and mPCIe
have to be accessible. Ensure sufficient distance on the right. For the position
of the connections, refer to chapter 10.1.3 "Internal connections for USB,
mSATA modules and mPCIe modules" on page 22
IndraControl VPB 40.4
21/57
Mounting, demounting and electric installation
R911376309_Edition 02 Bosch Rexroth AG