9.2 Connection points
9.2.1
General information
The connection points at control sections are equipped with spring terminals
and screw terminal blocks.
To connect 2 conductors in one terminal connecting point:
Use stranded wires with min. 0.5 mm
2
and max. 1.0 mm
2
Use wires of the same cross section
Use TWIN ferrules
9.2.2 Connection points with spring terminals
Spring
terminals can be wired with wire ends equipped with or without fer‐
rules. Preferably use wire ends without ferrules.
When assembling the connections, make sure
that the stripped length of the wire ends is 10 mm
that all strands of a stranded wire are placed in the funnel of the terminal
connector
not to use solid wires, where possible
to use appropriate crimping tools for the wire ends with ferrules
9.2.3 Connection points with screw terminal blocks
On screw terminal blocks, use wire ends with ferrules. Make sure to use ap‐
propriate crimping tools.
When assembling the connections, make sure that all strands of a stranded
wire are placed in the funnel of the terminal connector.