Loading...
9-4 DST / DLT transformers ECODRIVE DKC02.1 Drive Controller
DOK-ECODRV-DKC02.1****-PRJ2-EN-P
9.3 Electrical connection of the DKC via transformer
AP0249D4.fh5
NFD
DKC
PE
L1
L2
L3
PE
L1
L2
L3
Q1
K1
3 x AC
50...60 Hz
E'
L1'
L2'
L3'
X8
L1
L2
L3
1
2
3
DST
Mains filter
Power connection at X8:
3xAC380...480 V with DKC**.*-040-7-
Power
connection
for further
DKCs
1)
Protective conductor connection 10mm
2
(EN50178)
1)
Fig. 9-3: Power connection via a three-phase autotransformer
9.4 Type code
Rated output voltage
(phase to phase)
AC 230 V
Rated output voltage
(phase to phase)
AC 380 V; AC 415 V
Mounting style
horizontal mounting
vertical mounting
Rated power in kVA
20 kVA
Product group
Three-phase autotransformer
Three-phase isolating autotransformer
Type code fields:
Example:
Connection symbol
YYNO
DST 20,00/S/380,415-220-YYNO
TL0201D4.fh5
DST
DLT
20,00
L
S
380,415
220
YYNO
Fig. 9-4: Type codes for transformers
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01