5) Use the numeric keys [0] to [9] to program the new
poll rate in seconds (0000 to 1300), then press [OK]
to save and exit or press [MENU] to exit without
saving.
Comms > IP > L563
Acknowledge Wait Time
MENU 5-6-3
0 1 0
SECONDS
This feature requires rmware version 2.10 or higher
This menu allows the installer to program the
acknowledge wait time in seconds for both Destination 1
and/or Destination 2. The acknowledge wait time can be
programmed between 1 and 255 seconds (0 = Disabled).
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [6] + [3] + [OK]. The keypad will prompt
you to enter which destination (destination 1 or 2)
that you want to program the acknowledge wait
time.
dst=
3) Enter the destination number (1 or 2) required,
then press [OK]to select.
4) The keypad will display the current acknowledge
wait time.
d= 010
5) Use the numeric keys [0] to [9] to program the new
acknowledge wait time in seconds (000 to 255),
then press [OK] to save and exit or press [MENU] to
exit without saving.
Comms > IP > L564
IP Format
MENU 5-6-4
0 = Conettix 0 1
1 = Conettix NNC (Anti Replay)
2 = CSV IP ALARM
This feature requires rmware version 2.10 or higher.
This menu allows the installer to program which IP format
the control panel will report to the base station receiver.
1) Enter your Installer PIN + [MENU].
2) Enter [5] + [6] + [4] + [OK]. The keypad will prompt
you to enter which destination (destination 1 or 2)
that you want to program the acknowledge wait
time.
dst=
3) Enter the destination number (1 or 2) required,
then press [OK]to select.
4) The keypad will display the current IP format.
d= 00
5) Use the numeric keys [0] to [9] to program the new
IP format required, then press [OK] to save and exit
or press [MENU] to exit without saving.
dSt= Enter Destination 1 or Destination 2 then
press [OK].
Comms > IP > L565
Retry Count
MENU 5-6-5
0 3
This feature requires rmware version 2.10 or higher.
This menu allows the installer to program the number of
attempts that the system will try to communicate via TCP/
IP to the base station receiver for both Destination 1 and/
or Destination 2. The retry count can be programmed
between 1 and 15 (0=Disabled).
1) Enter your Installer PIN + [MENU].