Solution 6000-IP
Installation Manual Device Programming
10-11
Bosch Security Systems 10/22 BLCC615I
Device > RF Devices >
Supervision Time
MENU 6-2-1
(*** System Wide Parameter ***)
0 2 4
HOURS
This menu sets the global RF supervision time for all RF
devices connected to the system.
RF transmitters (sensor devices) will send a supervisory
test signal approximately once every hour. The RF receiver
expects to receive this supervisory signal from every
transmitting device within the supervision time period.
The panel will send a Missing report to the base station for
any RF device that fails to report within the supervision
time.
1) Press [MENU] + [6] + [2] + [1]. The keypad will
display the current RF supervision time.
Supervision Time
024 Hours
Press 0-9 OK to SAVE
2) Using the numeric keys, enter the number of hours
for the RF supervision time. Valid times are 0 - 255
hours, 0 = No Supervision.
3) Press [OK] to save and exit or press [MENU] to exit
without saving.
Device > RF Devices >
RF Device Options
MENU 6-2-2
1 Display RF Tamper Y
2 Report RF Tamper Y
3 Report RF Low Battery Y
4 Report Lost RF Devices Y
5 Open Zone On Lost RF N
6 Audible Keyfob Panic Y
7 Report Keyfob Panic Y
8 Keyfob Func Part On Y
This menu option allows you to configure various options
and functions for RF devices connected to the system.
1) Press [MENU] + [6] + [2] + [2]. The keypad will
display the current RF Device Options.
Display RF Tamper
Report RF Tamper
Report RF Low Battery
Press OK ON OFF MENU
2) Use the up and down arrow keys to highlight the
option then press the [ON] key to enable or the
[OFF] key to disable.
3) Repeat Step 2 until all options are programmed as
required, then press [OK] to save and exit or press
[MENU] to exit without saving.
Display RF Tamper
Setting this option will cause the keypad to display the
RF zone when a tamper condition occurs.
Report RF Tamper
Setting this option will cause the panel to send an RF
Device Faulted report to the base station when the
devices tamper curcuit is tripped. A restore report will be
sent when the tamper circuit is resealed.
Report RF Low Battery
Setting this option will cause the panel to send a report
to the base station when the RF device signals to the
panel that it has a low battery condition.
Report Lost RF Devices
Setting this option will cause the panel to send a report
to the base station if the panel detects that an RF device
is missing.
Open Zone On Lost RF
Setting this option will cause the panel to show a zone
fault on the keypad for any RF devices that are missing.