6720892984 (2019/02) US SSB
30 | Main control
Specic Parameters Level
(Default) Value Settable
°C °F °C °F
Warm_Weather_Shutdown
Set max. outdoor temp. Above this temperature heat demand is blocked.
[°C/°F] 2: Installer 22 72 0..35 32..95
Boost_Temperature_Incr
CH setpoint increment when heat demand remains beyond Boost_Time_
Delay.
[°C/°F] 2: Installer 0 0 0..20 0..36
Boost_Time_Daily [min] 2: Installer 20 min. 1..120
CH_Setpoint_Diff
Adjusts the calculated CH setpoint.
[°C/°F] 1: User 0 0 -10..10 -18..18
CH_Reset_Curve_Comp
Extra compensation
[°C/°F] 1: User 0 0 -10..10 -18..18
Status variables Level
Value/Range
°C °F
Actual_CH_Setpoint
20..90 68..194
Calculated CH setpoint based on outdoor reset curve.
5.2.1.3 CH mode 2 – Central Heating with full outdoor temperature reset
When
CH_Mode
is set to 2, full weather compensator is chosen. For this mode an outdoor sensor has to be connected.
The
CH_Setpoint
is calculated on the same way as described in paragraph”5.2.1.2 CH mode 1 - CH with an outdoor temperature reset and thermostat
control” pag. 28.
The
CH_Setpoint
can be calculated with an extra correction described in paragraph “5.2.1.2 CH mode 1 - CH with an outdoor temperature reset and
thermostat control” pag. 28
However, the demand does not depend on the RT input but on the outdoor temperature and the outdoor reset setpoint.
When the outdoor temperature is below
Warm_Weather_Shutdown
(settable) CH demand is created.
During the night an input signal from an external clock can lower the
CH_Setpoint
.
When the RT input opens
CH_Setpoint
will be decreased with
Night_Setback_Temp
.
The RT input does not inuence the CH demand directly!
Relevant variables
Parameters Level
(Default) Value Settable
°C °F °C °F
CH_Mode 2: Installer 0 0, 1, 2, 3, 4
Night_Setback_Temp
Sets the desired CH setpoint decrease, when the clock (RT) input is closed.
[°C/°F] 2: Factory 10 18 0..50 0..90
Warm_Weather_Shutdown
Set max. outdoor temp. Above this temperature heat demand is blocked.
[°C/°F] 2: Installer 22 72 0..35 32..95
CH_Setpoint_Diff
Adjusts the calculated CH setpoint
[°C/°F] 2: User 0 0 -10..10 -18..18