General recomendation
• Durante la obra bañera (tina) o hidromasaje siempre debe estar cubierto por un plástico protector para evitar ralladuras y maltratos.
• La bañera (tina) o hidromasaje debe ser instalado después de que se realice todo el enchape y trabajos locativos en el baño.
• La bañera (tina) o hidromasaje con el auto portante tienen la altura necesaria para permitir un fácil acceso, por lo tanto NO se debe colocar
rellenos o bases extra para aumentar la altura.
• Verifique que no haya fugas en las mangueras y en la motobomba, antes de finalizar la instalación.
• Verifique que la manguera de succión este amarrada y puesta hacia arriba de manera que por esta no se salga el agua y haya filtraciones.
• Cuando su hidromasaje sea instalado en exteriores, los motores NO DEBEN UBICARSE en un lugar donde se mojen.
• No reubicar ninguno de los componentes y/o equipos del hidromasaje.
• Si su equipo tiene sistema de aeroterapia, recuerde ubicar el blower (soplador) 15 cm alejado del muro, de lo contrario puede sufrir
recalentamiento.
these latest data would be used.
Superior opening start at a height greater than or equal to 180cm from the ground and the lower than a distance less than or equal to 30cm.
- If it connects other spaces on different floors:
Have openings on doors or floors with a minimum free area equal to 44 cm2 per kilovatio of nominal or joint nominal power of all gas artifacts installed
in the confined space. (15L - 1373 cm2 35cmx40cm and 18L - 1628 cm2 40cmx41cm).
- If you connect with the outside:
Have two (2) openings one upper and one lower each with a minimum free area of 6cm2 for each kilowatt of nominal or joint nominal power of all gas
artifacts installed in the confined space. (15L - 187.2 cm2 12cmx16cm and 18L - 222 cm2 14cmx16cm).
Opening or upper grid Start at a height greater than or equal to 180cm from the ground and the lower than a distance less than or equal to 30cm.
Electrical needs: The connection must be adequate for the need for electrical consumption of each heater of 50 W.
the flame of the heater in case of working with a gas pipette, does not easily throw the alarm for little gas flow, since it is demanding its maximum flame
• If a lower temperature is set to 55°C, it will directly affect the times in which the bathtub heats up (it will take longer).
• Minimum space and ventilation for heater installation:
Ventilation regulations must be complied with when a space is confined (indoor enclosure with a volume less than 3.4m3 for each nominal kilowatt added
or set of all installed gas appliances).
- Nominal consumption of bosch heater 15L = 31.2kW
- Nominal consumption of bosch heater 18L = 37kW
So for the installation site not to be considered confined space, it must have for the 15L bosch heater a volume greater than or equal to 106 m3
(approximately 5 m x 5 m x 4.3 m), and for the 18L bosch heater a volume greater than or equal to 125.8 m3 (approximately 5 m x 5 m x 5.1 m).
So, if it is a confined space, these ventilation considerations must be met:
- If you connect to other spaces on the same floor:
Have two (2) openings one upper and one lower each with a minimum free area equal to the highest value between 645 cm2 or 22cm2 per kilovatio of
nominal or joint nominal power of all gas artifacts installed in the confined space. (15L - 686.4 cm2 20cmx35cm and 18L - 814 cm2 26cmx32cm) In this case