Appendix
41
Uni Condens 8000 F – 6720867056 (2016/10)
14 Appendix
14.1 Specifications
Table 18 Specifications
14.2 Values for calculating the flue gas
Table 19 Operating temperatures 50/30 °C and 80/60 °C
Unit Boiler type
800 1000 1200
Permissible flow temperature
1)
1) Safety limit (high limit safety cut-out).
Maximum possible flow temperature with control units of the seriesCFB 800/CFB 900= safety limit (STB) - 18 K.
Example: safety limit (STB) = 100 °C, maximum possible flow temperature = 100 – 18 = 82 °C.
Maximum possible flow temperature withCC 8000control units control units of the seriesCFB 800/CFB 900= safety limit (STB) - 12 K.
Example: safety limit (STB) = 99 °C, maximum possible flow temperature = 99 – 12= 87 °C.
°C 110 110 110
Permitted operating pressure bar 6 6 6
Product ID no. CE-0085 CM 0479 CE-0085 CM 0479 CE-0085 CM 0479
Weight (empty) Net kg 1540 1792 1822
Total weight in operation
2)
2) Specification without burner
Gross kg 2470 2992 3012
Water Content Itr 930 1200 1190
Hot gas volume Itr 1020 1310 1320
Rated heat input
[burner output Qn (Hi)]
Full load, max. kW 742 928 1114
Partial load 30% kW 223 278 334
Available draught Pa Subject to burner
(50)
3)
3) Value in brackets is the recommended draught.
Subject to burner
(50)
3)
Subject to burner
(50)3)
Resistance of products of
combustion
mbar 6.4 6.5 7.5
Unit Boiler type
800 1000 1200
Values at system temperature 50/30 °C
Rated output, gas Full load kW 800 1000 1200
Partial load 30 % kW 243 303 364
Rated output oil Full load kW 770 962 1155
Partial load 30 % kW 233 292 351
CO
2
content Gas/oil % 10 / 13 10 / 13 10 / 13
Flue gas temperature
1)
1) Arithmetical flue gas temperature used for cross-sectional calculation according to EN 13384 (average value across product line). The actual flue gas temperature may differ
from this, subject to burner setting and actual system temperature.
Full load °C 40 40 40
Partial load 30 % °C 30 30 30
Flue gas mass flow rate Full load kg/s 0.300 0.375 0.451
Partial load 30 % kg/s 0.089 0.112 0.134
Values at system temperature 80/60 °C
Rated output, gas Full load kW 725 906 1090
CO
2
content Gas/oil % 10 / 13 10 / 13 10 / 13
Flue gas temperature
1)
Full load °C 66 66 66
Partial load 30 % °C 36 36 36
Flue gas mass flow rate Full load kg/s 0.316 0.395 0.475
Partial load 30 % kg/s 0.095 0.118 0.142