Technical description | 17
6 720 807 794 (2013/04)UNIMAT
For information and instructions regarding the
requirements for the boiler installation room, see
chapter 10.2, page 67.
These dimensions are designed for 100-mm thick
insulation.
Connections W32.509 and W32.510 can be made on
the right hand or left hand side.
Dimensions given with ± 1 % tolerance; weights given
with ± 3 % tolerance.
Pipe thread to DIN 2999.
UNIMAT UT-L UT-L 2 UT-L 4 UT-L 6 UT-L 8 UT-L 10 UT-L 12 UT-L 14 UT-L 16 UT-L 18 UT-L 20 UT-L 22
H1 [mm] 1060 1060 1050 1150 1050 1205 1150 1215 1205 1240 1260
UNIMAT UT-L UT-L 24 UT-L 26 UT-L 28 UT-L 30 UT-L 32 UT-L 34 UT-L 36 UT-L 38 UT-L 40 UT-L 42 UT-L 44
H1 [mm] 1215 1330 1240 1260 1360 1330 1495 1550 1360 1495 1705
UNIMAT UT-L UT-L 46 UT-L 48 UT-L 50 UT-L 52 UT-L 54 UT-L 56 UT-L 58 UT-L 60 UT-L 62 UT-L 64
H1 [mm] 1550 1750 1705 1900 1750 2030 1900 2030 2150 2150
Table 9 Dimension H1 depends on the boiler size
UNIMAT UT-L UT-L 1 UT-L 2 UT-L 4 UT-L 6 UT-L 8 UT-L 10 UT-L 12 UT-L 14 UT-L 16 UT-L 18 UT-L 20
ECO 6 heat
exchanger
510/335 510/335 600/385 600/385 690/460 690/460 690/460 750/485 750/485 850/560 890/610
390/260 510/335 510/335 600/385 600/385 690/460 750/485 850/560
510/335 600/385 690/460
UNIMAT UT-L UT-L 22 UT-L 24 UT-L 26 UT-L 28 UT-L 30 UT-L 32 UT-L 34 UT-L 36 UT-L 38 UT-L 40 UT-L 42
ECO 6 heat
exchanger
890/610 890/610 930/635 930/635
1000/
685
1000/
685
1110/
760
1110/
760
1300/
885
1300/
885
1350/
985
850/560 890/610 930/635
1000/
685
1110/
760
1110/
760
1300/
885
750/485 890/610 890/610 930/635
1000/
685
1110/
760
UNIMAT UT-L UT-L 44 UT-L 46 UT-L 48 UT-L 50 UT-L 52 UT-L 54 UT-L 56 UT-L 58 UT-L 60 UT-L 62 UT-L 64
ECO 6 heat
exchanger
1350/
985
1550/
1060
1550/
1060
1600/
1085
1600/
1085
1750/
1185
1750/
1185
1900/
1285
2050/
1385
2050/
1385
2200/
1485
1300/
885
1350/
985
1550/
1060
1600/
1085
1600/
1085
1750/
1185
1900/
1285
1900/
1285
2050/
1385
1300/
885
1350/
985
1550/
1060
1600/
1085
1750/
1185
1900/
1285
1110/
760
1300/
885
1600/
1085
Table 10 Assignment of heat exchanger ECO 6 to boiler size
The tube bundles highlighted in bold
correspond to the assignment for the limit
output of the UNIMAT UT-L.
If the boiler is operated with low heating
output, a smaller flue gas heat exchanger
can also be selected under certain
circumstances.