Fitting | 69
6 720 807 794 (2013/04)UNIMAT
10.3 Installation dimensions
10.3.1 Installation room dimensions for the UNIMAT UT-L boilers
Fig. 47 UNIMAT UT-L boiler installation room dimensions
Allow extra space for sound insulation measures.
Maintain the specified wall clearances to facilitate
installation, service and maintenance work. Always
observe the local regulations.
H
A
1
L
1
L
2
A
2
6 720 642 347-60.1il
UNIMAT UT-L boiler Installation room dimensions
1)
1) The values given are a guide. They may differ subject to the individual system.
Boiler size Length Height Side clearance
2)
2) Subject to the burner; the values given are a guide. The burner door can pivot either to the right or left.
L
1
L
2
H A
1
A
2
[mm] [mm] [mm] [mm] [mm]
UT-L 1 2100 1000 3300 500 1200
UT-L 4 UT-L 2 2500 1000 3500 500 1300
UT-L 10 UT-L 6 2750 1000 3800 500 1300
UT-L 14 UT-L 8 3000 1000 4100 500 1300
UT-L 18 UT-L 12 3500 1000 4100 500 1300
UT-L 24 UT-L 16 3500 1000 4400 500 1500
UT-L 28 UT-L 20 3850 1000 4400 500 1500
UT-L 30 UT-L 22 4250 1000 4600 500 1550
UT-L 34 UT-L 26 4400 1000 5100 500 1650
UT-L 40 UT-L 32 4800 1000 5600 500 1800
UT-L 42 UT-L 36 5000 1000 On request 500 1800
UT-L 46 UT-L 38 5200 1000 On request 500 On request
UT-L 50 UT-L 44 5650 1000 On request 500 On request
UT-L 54 UT-L 48 5950 1000 On request 500 On request
UT-L 58 UT-L 52 6700 1000 On request 500 On request
UT-L 60 UT-L 56 7150 1000 On request 500 On request
UT-L 64 UT-L 62 7600 1000 On request 500 On request
Table 31 UNIMAT UT-L boiler installation room dimensions (dimensions of the boiler foundation
Tab. 39, page 78)

Table of Contents