Technical description | 13
6 720 807 794 (2013/04)UNIMAT
• For information and instructions regarding the
requirements for the boiler installation room, see
chapter 10.2, page 67.
• Equipment and complete dimensions according to
project-specific technical datasheet
• Dimensions given with ± 1 % tolerance
• These dimensions are designed for standard
insulation:
– 100-mm thick on back floor
– 100-mm thick on casing
• Sizing for the entrance:
– Transport height: additional clearance of at least
100 mm from dimension H1 or dimension H2
(valves fitted/not fitted)
– Minimum door clearance: additional clearance of at
least 200 mm from dimension B1 (valves fitted/not
fitted)
• The height of the boiler room is determined by the
system equipment. The clearance above the
maintenance platform should be at least 2 m.
UT-L 36 5250 6655 5320 5000 2274 3357 2655 2560 1850 4480 1520 240 1850
UT-L 38
4)
6000 6855 5520 5200 2424 3507 - 2710 2000 4650 1610 240 2000
UT-L 40 6500 6775 5090 4770 2124 3207 2505 2410 1750 4280 1510 220 1750
UT-L 42 7700 7235 5320 5000 2274 3462 2655 2560 1850 4480 1520 240 1850
UT-L 44
4)
8000 7683 5980 5655 2574 3762 - 2875 2100 5050 1630 280 2100
UT-L 46
4)
9300 7435 5520 5200 2424 3612 - 2710 2000 4650 1610 240 2000
UT-L 48
4)
10000 8285 6315 5990 2724 3912 - 3010 2200 5320 1890 280 2200
UT-L 50
4)
11200 8121 5980 5655 2574 3947 - 2875 2100 5050 1630 280 2100
UT-L 52
4)
12000 9086 7050 6725 2924 4297 - 3239 2440 6000 1890 280 2440
UT-L 54
4)
12600 7162 6315 5990 2724 4097 - 3010 2200 5320 1890 280 2200
UT-L 56
4)
14000 8803 7530 7170 3224 4597 - 3542 2600 6390 2100 320 2600
UT-L 58
4)
14700 9086 7050 6725 2924 4377 - 3239 2440 6000 1890 280 2440
UT-L 60
4)
16400 9566 7530 7170 3224 4677 - 3542 2600 6390 2100 320 2600
UT-L 62
4)
17500 9227 7980 7620 3424 4877 - 3770 2820 6790 2100 320 2820
UT-L 64
4)
19200 9227 7980 7620 3424 4877 - 3770 2820 6790 2100 320 2820
1) The dimension L1 is a recommended dimension and is subject to the burner manufacturer, type and the actual output. If a flue gas heat
exchanger is included in the standard delivery, the corresponding dimension of length in accordance with datasheet DA170/DA171
must be taken into account.
2) Minimum transport dimensions when valves, burner and terminal box have been removed (without cable conduit; with cable conduit +
75 mm on the right).
3) Maximum dimension above boiler connector, lifting lug or door mounting.
4) UNIMATIC positioned at the side.
UNIMAT
UT-L boiler
Output limit Dimension(s)
Flue gas
connection
Base frame
L1
1)
L2 L3 B1 H1
2)
H2 H3
3)
H4 L4 B2
H5
Channel
section
Type kW [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
Table 4 Main dimensions