Operation 19/46
RE51550-B/09.2019, BoschRexrothAG
The factory settings are as follows:
Definitions:
spx
/
Rpx
Switching point / switch-back point x
Dsx
/
DRx
Switch-on delay / switch-back delay for switching output x
axhI
/
axlO
maximum and minimum measured value for the output
a.OUx
Signal form of the analog output
OUx
Switching characteristic of the switching output x
h.UNI
/
T.UNI
Unit for humidity / temperature
R.OUx
Assignment of the switching outputxto filling level or temperature monitoring
DIs
Update rate of the display
lOC
Key lock
sj.OU
logged switching output
Dh.MM
Delay for recording the minimum / maximum humidity
DT.MM
Delay for recording the minimum / maximum temperature
Notice: In the case of customer-specific requirements, the default settings made
at the factory may deviate from the values listed here.
Version with 2 switching outputs:
Switching outputs Basic settings
spi
/
Rpi 80
%
/
75
%
eRR.
£
NO
Dsi
/
DRi
/
OUi 0
/
0
/
hNO h.UNI -i-
(%)
sp2
/
Rp2 60
/
55 c T.UNI c
Ds2
/
DR2
/
OU2 0
/
0
/
hNO R.OUi hUMi
R.OU2 TeMp
DIs fasT
lOC 000
Version with analog outputs:
Analog outputs
ai.hI
/
ai.lO
/
a.OUi 0
/
100
/
Ii
a2.hI
/
a2.lO
/
a.OU2 0
/
100
/
Ii
Diagnostic settings:
Diagnosis
sj.OU OUTi
Dh.MM 0.0
DT.MM 0.0