Settings in the service menu
53
Greenstar 8000 Style – 6720883855 (2019/01)
Table 19 Settings menu
Maintenance
Maintenance type • Without
• Burner run time
• Boiler run time
• Service date
• Landlord
Landlord:
This menu item allows a date to be set for annual service/
maintenance (End date). The service display appears as a
reminder 30 days before the scheduled date. A contact
telephone number (Installer tel. no.) is shown together
with service display. The tenant should call this number to
arrange a suitable maintenance date. A second reminder
appears at the scheduled date. If the service display is not
reset by the service engineer, the control unit limits the
functions 14 days after the scheduled date.
Reduced functions are set at Maint. reminder:
• DHW reduced: reduced comfort (max. 35 °C flow
temperature)
1)
• Boiler off: central heating and hot water
1)
functions
are set off.
Limit values
Max. flow temp. • 30...88 °C Limits the adjustment range for the flow temperature.
Max. DHW temp. • 30...80 °C Limits the adjustment range for the hot water
temperature.
Min. boiler outp. • "Minimum rated output"…"maximum rated
output"
Minimum heat output depending on code plug Max output
= 50 %
Heating curve
Req. odr. temp. • Off
•On
When connecting a weather-compensated control unit,
no adjustment to the appliance is required. The system
control unit optimises this setting. This service function
activates a simple, weather-compensated controller with
a linear heating curve. Depending on the on/off input, the
heating is switched on or off.
Htg. curve base • 20…90 °C This is only displayed if the controller was activated. This
can be used to set the base point of the heating curve,
which corresponds to a outside temperature of +20 °C.
Htg. curve end • 20...90 °C This is only displayed if the controller was activated. This
can be used to set the end point of the heating curve,
which corresponds to a outside temperature of -10 °C.
Summer mode • 0...16...30 °C This is only displayed if the controller was activated. This
can be used to set the temperature threshold at which
outside temperature the heating system is to switch to
summer mode.
Frost prot. • Off
•On
Frost temp. limit • 0...5…10 °C Temperature value for the system frost protection.
This service function is only available if the frost
protection function was activated. If the outside
temperature does not exceed the frost threshold
temperature, then the heating pump in the heating circuit
switches on.
1) Only available if optional integral diverter valve kit is fitted.
Menu item Settings/adjustment range Comment/restriction