Page 34 from 43 6 720 887 547 “SM FP_ErP MPP Europe 2018/08 en”
Technician Level
Comments
Access to
combustion
adjustments
Go to press ok and select
Ignition Burner Pressure
P0 contains the fan speed
setting (A0) and gas power
(L0) needed for ignition
Adjustment of air flow without
change gas conditions
See installation manual for
recommended setting
Adjustment of gas flow without
change air conditions
See installation manual for
recommended setting
Maximum power burner
adjustment after components
replacement / maintenance /
gas conversions
P1 contains the fan speed
setting (A1) and gas power
(L1) at maximum power
(depends on gas type /
model)
Adjustment of air flow without
change gas conditions
See installation manual for
recommended setting
Adjustment of gas flow without
change air conditions
See installation manual for
recommended setting
Minimum power burner
adjustment after repairs /
maintenance / gas conversions
P2 contains the fan speed
setting (A2) and gas power
(L2) at minimum power
(depends on gas type /
model)
(depends on gas type /
model)
Adjustment of air flow without
change gas conditions
See installation manual for
recommended setting
Adjustment of gas flow without
change air conditions
See installation manual for
recommended setting
Table 15 Combustion Power adjustments
Attention:
Values of L0 (in P0), L1 (in P1) or L2 (in P2) are made to increase / decrease
burner power measured in mbar and according correspondent gas type / appliance
capacity indicated in correspondent manual.
Values of A0 (in P0), A1 (in P1) or A2 (in P2) are made to increase / decrease fan
speed according info in the manual where a recommended value in indicated. To