When in solar mode, the unit remains in stand-by mode, because the expected outlet
water temperature is within an acceptable value when compared to the setpoint value. The
water heater must be able to go into solar mode, when water flow is detected if:
- inlet water temperature is higher than [Setpoint -1ºC];
or
- expected outlet temperature, calculated with minimum power, is higher than
[Setpoint +10ºC] or 60ºC (whichever is higher)
When the conditions disappear, the unit must be able to start-up the burner and run in
normal operation mode without the symbol in the display.