31 of 52© 2021 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM EN_TSM-2004-6A Advanced_Set-Up_20211012
SERIES 6A
ADVANCED SETUP GUIDE
11.2.4.36 Diagnostic value '59.mA - Setpoint current'
Here you can display the current setpoint in mA.
11.2.4.37 Diagnostic value '60.PZ Supply pressure PZ'
Indication on the display: #.### (bar)
###.## (psi)
#.### (MPa)
Purpose:
Shows the current supply pressure PZ. The value refers to the
pres‐sure unit assigned in "U1.PUNIT".
If the supply pressure is the same as the pressure level of the envi‐
ronment, the pressure value shown in the display is 0. Depending on
the height at which you use the positioner, the displayed pressure
value is ≠0. Press the button for at least 5 seconds to set the value
to 0. "rESEt" is shown in the display for as long as you press the
button. This calibration is only possible if the displayed pressure
value is in the following pressure range:
-0.500 … 0.500 (bar)
-72.51 … 72.51 (psi)
-0.050 … 0.050 (MPa)
If the pressure value displayed is outside of the pressure range, "no‐
toL" is shown in the display when you attempt to set the value to 0.
11.2.4.38 Diagnostic value '61.P1 - Actuating pressure Y1'
Indication on the display: #.### (bar)
###.## (psi)
#.### (MPa)
Purpose:
Shows the current actuating pressure Y1. The value refers to the
pressure unit assigned in "U1.PUNIT".
If the actuating pressure is the same as the pressure level of the
environment, the pressure value shown in the display is 0.
Depending on the height at which you use the positioner, the dis‐
played pressure value is ≠0. Press the button for at least 5 seconds
to set the value to 0. "rESEt" is shown in the display for as long as you
press the button. This calibration is only possible if the displayed
pressure value is in the following pressure range:
-0.500 … 0.500 (bar)
-72.51 … 72.51 (psi)
-0.050 … 0.050 (MPa)
If the pressure value displayed is outside of the pressure range, "no‐
toL" is shown in the display when you attempt to set the value to 0.
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
232 Operating Instructions, 10/2020, A5E00074631-AF

Other manuals for Bray 6A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bray 6A series and is the answer not in the manual?

Bray 6A series Specifications

General IconGeneral
BrandBray
Model6A series
CategoryValve Positioners
LanguageEnglish

Related product manuals