32 of 52© 2021 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM EN_TSM-2004-6A Advanced_Set-Up_20211012
SERIES 6A
ADVANCED SETUP GUIDE
11.2.4.39 Diagnostic value '62.P2 - Actuating pressure Y2'
Indication on the display: #.### (bar)
###.## (psi)
#.### (MPa)
Purpose:
Shows the current actuating pressure Y2. The value refers to the
pressure unit assigned in "U1.PUNIT".
If the actuating pressure is the same as the pressure level of the
environment, the pressure value shown in the display is 0.
Depending on the height at which you use the positioner, the dis‐
played pressure value is ≠0. Press the button for at least 5 seconds
to set the value to 0. "rESEt" is shown in the display for as long as you
press the button. This calibration is only possible if the displayed
pressure value is in the following pressure range:
-0.500 … 0.500 (bar)
-72.51 … 72.51 (psi)
-0.050 … 0.050 (MPa)
If the pressure value displayed is outside of the pressure range, "no‐
toL" is shown in the display when you attempt to set the value to 0.
11.2.4.40 Diagnostic value '63.PZMAX Maximum supply pressure PZ
Indication on the display: #.### (bar)
###.## (psi)
#.### (MPa)
Purpose:
The supply pressure PZ is continuously monitored and the maximum
value (min/max pointer) is displayed.
The min/max pointer can be reset via HART communication.
11.2.4.41 Diagnostic value '64.N_MIN - Event counter violations of lower limit PZ'
Display range:
Purpose:
0 ... #####
Each new measured value of the supply pressure PZ is compared
with the value set in "U5.PZMLL". The counter increases when the
supply pressure falls below the con󹪝gured limit.
The counter can be reset via HART communication at the same time
as the "65.N_MAX" counter.
Diagnostics and troubleshooting
11.2 Diagnostics
SIPART PS2 with 4 to 20 mA/HART
Operating Instructions, 10/2020, A5E00074631-AF 233

Other manuals for Bray 6A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bray 6A series and is the answer not in the manual?

Bray 6A series Specifications

General IconGeneral
BrandBray
Model6A series
CategoryValve Positioners
LanguageEnglish

Related product manuals