EasyManua.ls Logo

BRUEL & KJAER VIBROCONTROL 8000 - 13.4.1.2 Compression Deviation (PI Only); 13.4.1.3 High Trigger, Low Trigger (0,0) - Special Case

BRUEL & KJAER VIBROCONTROL 8000
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 104 of 188
© Brüel & Kjaer Vibro S1079330.002 / V04
Technical alterations reserved
EN
13.4.1.2 Compression Deviation (PI Only)
The OSI Soft PI Data Archive uses a “swinging door” algorithm to compress time-series data. The
algorithm stores only what is needed to provide an accurate data history. The sensitivity of the
algorithm is controlled by the Compression Deviation setting. Compression Deviation should be set at
twice the Exception Deviation value.
When the machine is in a transient condition, the SETPOINT PI Adapter can temporarily bypass PI
Compression. This allows higher resolution data to be stored and improves diagrams (Bode, Polar,
etc.) used for startup and shutdown analysis (see 13.4.1).
NOTE!
To learn more about Exception Deviation and Compression Deviation see the many tutorials
available on the OSI Soft YouTube channel.
13.4.1.3 High Trigger, Low Trigger (0,0) Special Case
When Low Trigger and High Trigger are both set to zero the SETPOINT PI/XC Adapter uses an
algorithm to detect when the machine is in transient mode. The algorithm is continuously executed
(every second or faster) and performs as follows:
Calculate max speed, min speed, and delta speed (over the last 30 seconds)
Evaluate using current speed, and look-up table
For systems using the PI/XC Adapter 7.x or later the algorithm is shown in Table 13-10. For systems
using CMS 6.x or earlier the algorithm is shown in Table 13-11.
Current Speed
If Delta Speed is…
Machine Condition =
Below 7,500 RPM
Above 5 RPM
Transient
7,500 to 60,000 RPM
Above (max speed * 0.002) RPM
(Typically, 15 to 120 RPM)
Transient
Above 60,000
Above (max speed * 0.004) RPM
(Typically, above 240 RPM)
Transient
Table 13-10) Algorithm (CMS 7.x and later)
Current Speed
If Delta Speed is…
Machine Condition =
Below 1,000 RPM
Above 2 RPM
Transient
1,000 to 60,000 RPM
Above (max speed * 0.002) RPM
(Typically, 2 to 120 RPM)
Transient
Above 60,000
Above (max speed * 0.004) RPM
(Typically, above 240 RPM)
Transient
Table 13-11) Algorithm (CMS 6.x and earlier)

Table of Contents