© Brüel & Kjaer Vibro ● S1079330.002 / V04 ● █ Page 109 of 188
Technical alterations reserved!
Brüel & Kjaer Vibro │ Instruction
VC-8000 MPS
Content
EN
15.1.6 Asset Level 1 & Asset Level 2
Asset Level 1 and Asset Level 2 are used in conjunction with the tag name, to identify the machine
train, machine case, and location of the sensor.
Asset Level 1 and Asset Level 2 are also used as major (level 1) and minor (level 2) groupings. These
groups are used to assist in configuring the following:
• Relay Logic (See 17.3.1)
• Rack Touch Screen Display (see 12.2.3)
• Rack Maintenance Software (see 12.2.3)
15.1.7 Alert & Danger Latching
Alert & Danger Latching allows the user to set alarms to Latching or Non-Latching.
Consider Non-Latching alarms (with Latching Relays) for improved event list management.
Non-Latching alarms update the event list when the channel leaves alarm. In contrast, a
latched alarm updates the event list when the user resets the alarm.
15.1.8 Display Order
This setting controls the position of the channels on the
Maintenance software screens. Channels are grouped by
Asset Level 2, and then ordered by the Display Order
setting (see section 11.7).
If the Display order column is not used (all values are set
to zero), the channels will be ordered by slot and then by
channel.
15.2 Customize Transducer View
Use the Customize Transducer view to change
transducer settings.
15.2.1 Barrier
When the box is checked, the transducer scale factor is
adjusted for barriers. No other function is performed
with this setting.
15.2.2 Scale Factor (mV) & Unit
This setting allows the user to set Transducer scale factor (mV) and units. When you select a
transducer, this value is set automatically depending on the transducer selected. The scale factor can
be changed if needed.
15-2 ) Display Order column
15-3) Display Order column