16 Configuring - Measurements Tab
Modify alarms and full-scale range settings from the Measurements tab. Use the Primary view
selection to simplify the layout (this will hide all 1X, 2X, and Gap measurements).
Figure 16-1) Measurements Tab
16.1 Primary and All Views
Both the Primary view and the All view show the
same columns headers. The Primary removes all
1X, 2X, Gap, etc. measurements and only shows
the primary measurement for the channel; for
example, the Direct measurement on a Radial
Vibration channel. The definition of each column
header is explained below.
16.1.1 Measurement Name
The Measurement column shows each measurement for the channel. Most channel types have
multiple measurements. For example, Direct, Gap, 1X, 2X, on a Radial Vibration channel.
The name of the measurement is editable and can be modified (although it is rare to do so).
16.1.2 Maximum & Minimum Scale, Units & Sub Units
The measurement’s maximum and minimum scale values and unit. For example: 0-10 mils pp, or
0-25 µm pp.
These values are used on the local display panel, and in CMS. They are also used when sending
scaled Modbus data. For example, the Modbus value (0-65535) would be scaled to the range
configured on the Radial Vibration channel (0-10 mils pp).
Figure
16-2) Primary and All views